FLD-xRTD is a self-powered intrinsically safe Monitoring module designed for rapid response to detecting leaks of refined products or crude oils in extreme environmental conditions. The monitoring module is engineered for outdoor installation in challenging environmental conditions. Its measurement frontend is designed for interfacing with reusable, fully passive hydrocarbon sensor cables and sensing probes manufactured by Naftosense.
The multiplexed architecture of the monitoring module allows up to 8 individual sensor sections not exceeding 82 ft (25 m) per FLD-xRTD.
Advanced measurement techniques and data treatment algorithms are used to provide intelligent thresholding for eliminating the nuisance alarm due to the presence of motor/lube oils, greases, residues of old leaks, etc.
The variable resistance outputs of the Monitoring module emulate standard Pt100 RTD for direct interfacing to 3rd party temperature transmitters. This feature allows cost-efficient interfacing to third-party wireless transmitters available worldwide and easy testing and troubleshooting using a regular multimeter.
Typical Detection Time at 68°F (20°C) with FLD-HSC Sensor Cable | |
Unleaded Gasoline | 1 minute 30 seconds |
Diesel/Jet Fuel | 2 to 3 minutes |
Light Crude Oils | 6 to 8 minutes |
Heavy Crude Oils | 12 to 16 minutes |
Motor/Hydraulic/Silicone Oils | 12 to 25 minutes |
OUT1 – Status and Relative Contamination | OUT2* - Status or Section Identification |
Normal status: 100 Ohms | Normal status: 100 Ohms |
Sensor String Break: 60 Ohms | Sensor String Break: 60 Ohms |
Hardware failure/Low battery: 75 Ohms | Hardware failure/Low battery: 75 Ohms |
Leak alarm w/level: 151 – 300 Ohms (32 steps) | Number of sensor section in leak alarm: sensing cable number (depending on 1, 3, or 8 channel monitoring modules used) |
Battery too low, device off: > 1 kOhms | Battery too low, device off: > 1 kOhms |
* On request, OUT2 may be used for coding other parameters. Please contact Naftosense for details.
Technical Data | |
Dimensions | 2.52" x 2.283" x 1.378" (64 x 58 x 35 mm) |
Weight | 0.5 lb. (225 g) |
Fire Rating | UL94-HB |
Ingress Rating | IP67/NEMA4X – suitable for outdoor/direct burial |
Operating Temperature Range | -67°F to 212°F (-55°C to 100°C) |
Supply Voltage | 3.6 VDC |
Operating Life | 10 years minimum |
Mounting | Wall-mounted with external mounting brackets |
Hazardous Locations Classification Model FLD-F4RTD | IS/ I/ 1/ CD/ T4 ; I/ 0/ AEx/ ia IIB T4 ; Class I, Zone 0, Ex ia T4 Class I, Div. 1, Groups C,D; T4 II 1 G Ex ia IIB T4 Ga |
Hazardous Locations Classification Model FLD-T3RTD | IS/ I/ 1/ CD/ T3 ; I/ 0/ AEx/ ia IIB T3 ; Class I, Zone 0, Ex ia T3 Class I, Div. 1, Groups C,D; T3 II 1 G Ex ia IIB T3 Ga |
Warranty | 10 years |
Warning! This is an agency-approved product. It shall be installed according to the corresponding classified location certificates. Any deviation from the conditions of use defined in the Control Drawing is strictly prohibited. The device contains encapsulated non-replaceable lithium battery. Please dispose it as required by the relevant local regulations.
Product Codes | |
FLD-F4RTD-1 | Single-channel Field box with 1 x Pt100-RTD-compatible output. Hazardous area – T4 rated |
FLD-F4RTD-3 | Three-channel Field box with 2 x Pt100-RTD-compatible outputs. Hazardous area – T4 rated |
FLD-F4RTD-8 | Eight-channel Field box with 2 x Pt100-RTD-compatible outputs. Hazardous area – T4 rated |
FLD-T3RTD-1 | Single-channel Field box with 1 x Pt100-RTD-compatible output. Hazardous area - T3 rated |
FLD-T3RTD-3 | Three-channel Field box with 2 x Pt100-RTD-compatible output. Hazardous area - T3 rated |
FLD-T3RTD-8 | Eight-channel Field box with 2 x Pt100-RTD-compatible output. Hazardous area - T3 rated |