The FLD-MXM-PS is an advanced acquisition module designed for reliable detection and location of unwanted presence of polar solvents such as alcohols, acetone/MEK, etc. It can also be used to detect hydrocarbon liquids and their vapors. The measurement frontend is engineered for interfacing with passive sensing probes offered by Naftosense. Advanced measurement techniques and data treatment algorithms are used to provide quick detection in a wide temperature range. The status of the module is indicated by embedded LED’s for instant identification of the sensor string in alarm. The module provides the leak alarm level allowing adjustable thresholding from the associated monitoring panel. The FLD-MXM-PS module has built-in specific algorithm for tracking the electrical conductivity between the detection cable sensor wires for very efficient reduction of the false positives due to condensation, conductive dust, dirt, etc. (intelligent thresholding).
| Typical Detection Time at Ambient Temperature | |
| 20%-100% vol. alcohol in water | 2 to 2.5 minutes |
| Gasoline and other hydrocarbons | 30 seconds to 10 minutes |
| Hydrocarbon vapors | 3 to 4 minutes |
| Compatible Sensors | |
| FLD-PSP-xx | Sensing probe for polar solvents and hydrocarbons for outdoor applications - storage tank farms, chemical and petrochemical facilities, etc. |
| Technical Data | |
| Dimensions | 3.75" x 2.6" x 1.6" (95 x 65 x 40 mm) |
| Weight | 0.76 lb (245 g) |
| Fire Rating | UL94-V0 |
| Ingress Rating | IP67/NEMA4X - suitable for outdoor/direct burial |
| Operating Temperature Range | -40°F to 176°F (-40°C to 80°C) |
| Power Supply Voltage Range | 10 - 20 VDC |
| Power Consumption | 20mA max. |
| Mounting | Wall-mounted with external mounting brackets |
| Hazardous Locations Classification | IS/ I/ 1/ CD/ T4 ; I/ 0/ AEx/ ia IIB T4 ; Class I, Zone 0, Ex ia T4 Class I, Div. 1, Groups C,D; T4 II 1 G Ex ia IIB T4 Ga |
| Tested and Approved Sensors | FLD-PSP |
| Approved Monitoring Devices | FLD-SMP, FLD-ERBC, FLD-TSP7, FLD-TSP10 |
| Warranty | 10 years |
Warning! This is an agency-approved product. It shall be installed according to the corresponding hazardous location certificates. Any deviation from the conditions of use defined in the Control Drawing is strictly prohibited.
| Product Codes | |
| FLD-MXM-4-PS | Acquisition module for interfacing with Naftosense sensing probes for polar solvents and hydrocarbons (monitoring by ERBUS proprietary bus) |